Standards, Codes and Approvals for Fire Sprinkler Systems
APPLICABLE STANDARDS
Manufacturing Standards
- ASTM D1784 Specification for Rigid Poly(Vinyl Chloride)(PVC) Compounds and Chlorinated Poly(Vinyl Chloride)(CPVC) Compounds
- ASTM F437 Specification for Threaded Chlorinated Poly(Vinyl Chloride) CPVC Plastic Pipe Fittings, Schedule 80
- ASTM F438 Specification Socket-Type Chlorinated Poly(Vinyl Chloride) CPVC Plastic Pipe Fittings, Schedule 40
- ASTM F439 Specification Socket-Type Chlorinated Poly(Vinyl Chloride) CPVC Plastic Pipe Fittings, Schedule 80
- ASTM F442 Specification Chlorinated Poly (Vinyl Chloride) CPVC Plastic Pipe (SDR-PR)
Performance Standards
- ANSI/NSF Standard 14 Plastic Piping Components and Related Materials
- ANSI/NSF Standard 61 Drinking Water System Components – Health Effects
- ASTM F493 Specification for Solvent Cements for Chlorinated Poly(Vinyl Chloride) CPVC Plastic Pipe and Fittings
- UL 1887 Fire Test of Plastic Sprinkler Pipe for Flame and Smoke Characterization
- UL 1821 Outline of Proposed Investigation for Thermoplastic Sprinkler Pipe and Fittings for Fire Protection Service
Installation Standards
- ASTM F402 Practice for Safe Handling of Solvent Cements, Primers and Cleaners Used for Joining Thermoplastics Pipe and Fittings
- NFPA 13 Standard for Installation of Sprinkler Systems
- NFPA 24 Installation of Private Fire Service Mains and Their Appurtenance
- NFPA 25 Standard for the Inspection, Testing and Maintenance of Water Based Extinguishing Systems
- NFPA 13R Standard for Installation of Sprinklers in Residential Occupancies up to Four Stories in Height
- NFPA 13D Standard for Installation of Sprinkler Systems in One and Two Family Dwellings
- NFPA 90A Standard for Installation of Air Conditioning and Ventilating System
APPLICABLE MODEL CODES
- IBC, International Building Code
- ICC, International Code Council
- IMC, International Mechanical Code
- IPC, International Plumbing Code
- NBCC, National Building Code of Canada
- NSPC, National Standard Plumbing Code
- UMC, Uniform Mechanical Code
- UPC, Uniform Plumbing Code
LISTINGS, APPROVALS AND ENHANCEMENTS
- UL Listed (UL 1821)
- Can be flush at return air plenums
- Exposed system risers NFPA 13D, 13R
- Exposed basement NFPA 13D (solid wood joist)
- Extended coverage (exposed)
- 20' spacing on pendent in lieu of 15'
- 18' spacing on sidewall in lieu of 14'
- Use with combustible concealed sprinklers
- Tyco attic sprinkler head with wet system (to protect the floor below & feed main and ridge installation)
- Exposed sidewall sprinkler Listing for exposed pipe & fittings
- 24' extended coverage sidewall Reliable sprinkler, 12" drop, 155°F sprinkler head
- 18' extended coverage sidewall sprinkler, 12" drop,165°F sprinkler head
- 16' extended coverage sidewall sprinkler, 12" drop,175°F sprinkler head
- 14' standard coverage sidewall sprinkler, 12" drop, 200°F sprinkler head
- ULC or CUL Listed
- Factory Mutual Approved*
- Factory Mutual Approval exposed
- Factory Mutual Approval above drop-in ceilings
- Factory Mutual Approval w/ Soffi-Steel soffit covering system
- LPCB Approval
- VdS Approval
- Pressure rated system by Plastics Pipe Institute (PPI) both pipe and fittings
- Cell class 23547 CPVC pipe
- Cell class 24447 CPVC fittings
- Size available up to 3" in diameter
*as manufactured by Harvel, IPEX, Viking, NIBCO, Tyco and Durman Esquivel S A.
The above data is based on UL and FM reported Listings and Approvals as of 04/08/09. Check with UL or FM for future updates on Listings and Approval enhancements.